Cooper Bussmann BU-905U-L Wireless I/O Configuration Manual
Setting the Unit Secondary Address
The BU-905U-L-T supports a secondary address that lets you re-use the same unit address for multiple transmit-only units.
This is useful if your network has a large number of transmit-only units.
To reuse the same address:
NOTE: To use the same address you must have an existing BU-905U-L-T unit.
1. Create a new BU-905U-L-T.
2. BU-Config checks if you want to manually set the address:
3. Click Yes to manually set the address. If you click No BU-Config will select an unused address for the new unit, or if you click Cancel the new
module will not be created.
4. Select an address already used by a transmit-only unit that you want to reuse and click OK to set the address. If you click Cancel
BU-Config will return to the previous screen without creating a new unit:
5. BU-Config automatically assigns the secondary unit address to a different number:
6. Click OK to acknowledge the message.
7. You have created a unit with a new secondary address.
3A1579Rev1.4